DLI EPCR5 User's Guide
|
To enable the E-Stop switch, remove the yellow ring under the red button by pulling down on the label. To activate E-Stop Shutdown, press the red button. The event will be logged as:
emergency shutoff activated, all outlets off
Rotate the button clockwise to release and restore power. The event will be logged as:
emergency shutoff deactivated, normal outlet operation
WARNING! E-STOP DOES NOT SHUT DOWN THE UNSWITCHED (ALWAYS ON) OUTLETS!
The events will not be logged if the EPCR5 is running on battery.