DLI ISO32 Object Model Reference
|
object | modbus/ |
Object representing the Modbus/TCP slave configuration |
Retrieving the value is denied if not administrative user
This object contains the following items:
Sample requests
write command:
requests.put('http://192.168.0.100/restapi/modbus/',auth=auth,headers=headers,json=<...>)
Sample curl
read command:
curl --digest -u admin:1234 -H "Accept: application/json" "http://192.168.0.100/restapi/modbus/"
⇒
...
sum (boolean) | modbus/enabled/ |
Modbus/TCP slave enable status |
Retrieving the value is denied if not administrative user
Changing the value is denied if any of the following is true:
This sum represents a value in persistent storage.
This sum can assume the following values:
constant true | Enabled | The feature is enabled | |
constant false | Disabled | The feature is disabled |
Sample curl
write command:
curl --digest -u admin:1234 -H "X-CSRF: x" -X PUT -H "Content-type: application/json" -H "Accept: application/json" --data-binary "true" "http://192.168.0.100/restapi/modbus/enabled/"
Sample JS request
write command:
request.put({url:"modbus/enabled/",body:true});
array | modbus/outlets/ |
Properties related to exposing outlets via Modbus |
The value is subject to the following constraints: length of the value is equal to length of outlets
Retrieving the value is denied if not administrative user
Changing the value is denied if any of the following is true:
This array represents a value in persistent storage.
This array contains Outlet Modbus/TCP configuration elements.
Sample curl
write command:
curl --digest -u admin:1234 -H "X-CSRF: x" -X PUT -H "Content-type: application/json" -H "Accept: application/json" --data-binary "..." "http://192.168.0.100/restapi/modbus/outlets/"
Sample curl
outlet Modbus/TCP configuration creation command:
curl --digest -u admin:1234 -H "X-CSRF: x" -H "Content-type: application/json" -H "Accept: application/json" --data-binary "{\"allow_write\":false,\"allow_read\":true}" "http://192.168.0.100/restapi/modbus/outlets/"
See also Outlet Modbus configuration settings: Outlet Modbus/TCP configuration
object | modbus/outlets/N/ |
Properties related to exposing the outlet via Modbus/TCP |
The value is subject to the following constraints: outlets[index of the value]
This object contains the following items:
allow_read | Allow read |
allow_write | Allow write |
Sample JS request
deletion command (note that _outlet_modbus_tcp_configuration_index
is a variable):
request.delete({url:"modbus/outlets/"+_outlet_modbus_tcp_configuration_index.toString()+"/"});
Sample uom
library write command (note that _outlet_modbus_tcp_configuration_index
is a variable):
uom.modbus.outlets[_outlet_modbus_tcp_configuration_index]={allow_read=false,allow_write=false}
sum (boolean) | modbus/outlets/N/allow_read/ |
Outlet state is reported via Modbus/TCP |
Retrieving the value is denied if not administrative user
Changing the value is denied if any of the following is true:
This sum represents a value in persistent storage.
This sum can assume the following values:
constant true | Enabled | The feature is enabled | |
constant false | Disabled | The feature is disabled |
Sample requests
write command (note that _outlet_modbus_tcp_configuration_index
is a variable):
requests.put('http://192.168.0.100/restapi/modbus/outlets/'+str(_outlet_modbus_tcp_configuration_index)+'/allow_read/',auth=auth,headers=headers,json=True)
Sample curl
write command (note that :outlet_modbus_tcp_configuration_index
is a URL template argument):
curl --digest -u admin:1234 -H "X-CSRF: x" -X PUT -H "Content-type: application/json" -H "Accept: application/json" --data-binary "false" "http://192.168.0.100/restapi/modbus/outlets/:outlet_modbus_tcp_configuration_index/allow_read/"
sum (boolean) | modbus/outlets/N/allow_write/ |
Outlet state can be changed via Modbus/TCP |
Retrieving the value is denied if not administrative user
Changing the value is denied if any of the following is true:
This sum represents a value in persistent storage.
This sum can assume the following values:
constant true | Enabled | The feature is enabled | |
constant false | Disabled | The feature is disabled |
Sample uom
library write command (note that _outlet_modbus_tcp_configuration_index
is a variable):
uom.modbus.outlets[_outlet_modbus_tcp_configuration_index].allow_write=true
Sample requests
write command (note that _outlet_modbus_tcp_configuration_index
is a variable):
requests.put('http://192.168.0.100/restapi/modbus/outlets/'+str(_outlet_modbus_tcp_configuration_index)+'/allow_write/',auth=auth,headers=headers,json=False)
array | modbus/discrete_inputs/ |
Properties related to custom discrete inputs |
Retrieving the value is denied if not administrative user
Changing the value is denied if any of the following is true:
This array represents a value in persistent storage.
This array contains Discrete input configuration elements.
Sample JS request
discrete input configuration creation command:
request.post({url:"modbus/discrete_inputs/",body:{"value":true,"allow_read":false,"name":"c5","index":37426}});
Sample uom
library discrete input configuration creation command:
uom.insert(uom.modbus.discrete_inputs,2,{allow_read=true,index=50636,name="aeqrwpw44",value=true})
See also Discrete input configuration settings: Discrete input configuration
object | modbus/discrete_inputs/N/ |
Properties related to a custom discrete input |
This object contains the following items:
name | Name |
index | Index |
allow_read | Allow read |
value | State |
Sample requests
read command (note that _discrete_input_configuration_index
is a variable):
print(requests.get('http://192.168.0.100/restapi/modbus/discrete_inputs/'+str(_discrete_input_configuration_index)+'/',auth=auth,headers=headers).json())
⇒
{'value': True, 'allow_read': True, 'name': 'z95', 'index': 21071}
Sample uom
library write command (note that _discrete_input_configuration_index
is a variable):
uom.modbus.discrete_inputs[_discrete_input_configuration_index]={allow_read=false,index=48116,name="o0",value=false}
string | modbus/discrete_inputs/N/name/ |
Discrete input name |
Retrieving the value is denied if not administrative user
Changing the value is denied if not administrative user
This string represents a value in persistent storage.
Sample CLI read command (note that discrete_input_configuration_index
is a variable):
uom get "modbus/discrete_inputs/${discrete_input_configuration_index}/name"
⇒
"f26"
Sample curl
write command (note that :discrete_input_configuration_index
is a URL template argument):
curl --digest -u admin:1234 -H "X-CSRF: x" -X PUT -H "Content-type: application/json" -H "Accept: application/json" --data-binary "\"puo97\"" "http://192.168.0.100/restapi/modbus/discrete_inputs/:discrete_input_configuration_index/name/"
number | modbus/discrete_inputs/N/index/ |
Zero-based index of discrete input (without 10...01 added) |
The value is subject to the following constraints: all of the following is true:
Retrieving the value is denied if not administrative user
Changing the value is denied if any of the following is true:
This number represents a value in persistent storage.
Sample uom
library write command (note that _discrete_input_configuration_index
is a variable):
uom.modbus.discrete_inputs[_discrete_input_configuration_index].index=5936
Sample uom
library read command (note that _discrete_input_configuration_index
is a variable):
print(uom.dump(uom.modbus.discrete_inputs[_discrete_input_configuration_index].index))
⇒
9703
sum (boolean) | modbus/discrete_inputs/N/allow_read/ |
Discrete input is readable via Modbus/TCP |
Retrieving the value is denied if not administrative user
Changing the value is denied if any of the following is true:
This sum represents a value in persistent storage.
This sum can assume the following values:
constant true | Enabled | The feature is enabled | |
constant false | Disabled | The feature is disabled |
Sample uom
library write command (note that _discrete_input_configuration_index
is a variable):
uom.modbus.discrete_inputs[_discrete_input_configuration_index].allow_read=true
Sample CLI write command (note that discrete_input_configuration_index
is a variable):
uom set "modbus/discrete_inputs/${discrete_input_configuration_index}/allow_read" "true"
sum (boolean) | modbus/discrete_inputs/N/value/ |
State of discrete input |
Retrieving the value is denied if not administrative user
Changing the value is denied if not administrative user
This sum represents a value in persistent storage.
This sum can assume the following values:
constant true | On | The input is on | |
constant false | Off | The input is off |
Sample requests
write command (note that _discrete_input_configuration_index
is a variable):
requests.put('http://192.168.0.100/restapi/modbus/discrete_inputs/'+str(_discrete_input_configuration_index)+'/value/',auth=auth,headers=headers,json=False)
Sample JS request
write command (note that _discrete_input_configuration_index
is a variable):
request.put({url:"modbus/discrete_inputs/"+_discrete_input_configuration_index.toString()+"/value/",body:true});
array | modbus/input_registers/ |
Properties related to custom input registers |
Retrieving the value is denied if not administrative user
Changing the value is denied if any of the following is true:
This array represents a value in persistent storage.
This array contains Input register configuration elements.
Sample uom
library read command:
print(uom.dump(uom.modbus.input_registers))
⇒
{{allow_read=true,index=28295,name="gd5",value=9208}}
Sample uom
library write command:
uom.modbus.input_registers={{allow_read=false,index=49649,name="jrx94",value=22331}}
See also Input register configuration settings: Input register configuration
object | modbus/input_registers/N/ |
Properties related to a custom input register |
This object contains the following items:
name | Name |
index | Index |
allow_read | Allow read |
value | State |
Sample CLI deletion command (note that input_register_configuration_index
is a variable):
uom remove "modbus/input_registers/${input_register_configuration_index}"
Sample JS request
deletion command (note that _input_register_configuration_index
is a variable):
request.delete({url:"modbus/input_registers/"+_input_register_configuration_index.toString()+"/"});
string | modbus/input_registers/N/name/ |
Input register name |
Retrieving the value is denied if not administrative user
Changing the value is denied if not administrative user
This string represents a value in persistent storage.
Sample requests
read command (note that _input_register_configuration_index
is a variable):
print(requests.get('http://192.168.0.100/restapi/modbus/input_registers/'+str(_input_register_configuration_index)+'/name/',auth=auth,headers=headers).json())
⇒
'yhfvsl3'
Sample requests
write command (note that _input_register_configuration_index
is a variable):
requests.put('http://192.168.0.100/restapi/modbus/input_registers/'+str(_input_register_configuration_index)+'/name/',auth=auth,headers=headers,json='nsmuhb4')
number | modbus/input_registers/N/index/ |
Zero-based index of input register (without 30...01 added) |
The value is subject to the following constraints: all of the following is true:
Retrieving the value is denied if not administrative user
Changing the value is denied if any of the following is true:
This number represents a value in persistent storage.
Sample JS request
read command (note that _input_register_configuration_index
is a variable):
request.get({url:"modbus/input_registers/"+_input_register_configuration_index.toString()+"/index/"},function(error,response,body) {console.log(body)});
⇒
6412
Sample requests
write command (note that _input_register_configuration_index
is a variable):
requests.put('http://192.168.0.100/restapi/modbus/input_registers/'+str(_input_register_configuration_index)+'/index/',auth=auth,headers=headers,json=22325)
sum (boolean) | modbus/input_registers/N/allow_read/ |
Input register is readable via Modbus/TCP |
Retrieving the value is denied if not administrative user
Changing the value is denied if any of the following is true:
This sum represents a value in persistent storage.
This sum can assume the following values:
constant true | Enabled | The feature is enabled | |
constant false | Disabled | The feature is disabled |
Sample JS request
read command (note that _input_register_configuration_index
is a variable):
request.get({url:"modbus/input_registers/"+_input_register_configuration_index.toString()+"/allow_read/"},function(error,response,body) {console.log(body)});
⇒
false
Sample requests
read command (note that _input_register_configuration_index
is a variable):
print(requests.get('http://192.168.0.100/restapi/modbus/input_registers/'+str(_input_register_configuration_index)+'/allow_read/',auth=auth,headers=headers).json())
⇒
False
number | modbus/input_registers/N/value/ |
State of input register |
The value is subject to the following constraints: all of the following is true:
Retrieving the value is denied if not administrative user
Changing the value is denied if not administrative user
This number represents a value in persistent storage.
Sample CLI read command (note that input_register_configuration_index
is a variable):
uom get "modbus/input_registers/${input_register_configuration_index}/value"
⇒
64029
Sample requests
write command (note that _input_register_configuration_index
is a variable):
requests.put('http://192.168.0.100/restapi/modbus/input_registers/'+str(_input_register_configuration_index)+'/value/',auth=auth,headers=headers,json=50091)
array | modbus/holding_registers/ |
Properties related to custom holding registers |
Retrieving the value is denied if not administrative user
Changing the value is denied if any of the following is true:
This array represents a value in persistent storage.
This array contains Holding register configuration elements.
Sample curl
read command:
curl --digest -u admin:1234 -H "Accept: application/json" "http://192.168.0.100/restapi/modbus/holding_registers/"
⇒
[{"allow_read":true,"name":"y36","value":48984,"allow_write":true,"index":59737}]
Sample CLI write command:
uom set "modbus/holding_registers" "[{\"allow_read\":false,\"name\":\"xt5\",\"value\":38341,\"allow_write\":false,\"index\":15605}]"
See also Holding register configuration settings: Holding register configuration
object | modbus/holding_registers/N/ |
Properties related to a custom holding register |
This object contains the following items:
name | Name |
index | Index |
allow_read | Allow read |
allow_write | Allow write |
value | State |
Sample requests
deletion command (note that _holding_register_configuration_index
is a variable):
requests.delete('http://192.168.0.100/restapi/modbus/holding_registers/'+str(_holding_register_configuration_index)+'/',auth=auth,headers=headers)
Sample requests
write command (note that _holding_register_configuration_index
is a variable):
requests.put('http://192.168.0.100/restapi/modbus/holding_registers/'+str(_holding_register_configuration_index)+'/',auth=auth,headers=headers,json={'allow_read': True, 'name': 'e9', 'value': 17517, 'allow_write': True, 'index': 7697})
string | modbus/holding_registers/N/name/ |
Holding register name |
Retrieving the value is denied if not administrative user
Changing the value is denied if not administrative user
This string represents a value in persistent storage.
Sample uom
library read command (note that _holding_register_configuration_index
is a variable):
print(uom.dump(uom.modbus.holding_registers[_holding_register_configuration_index].name))
⇒
"t3"
Sample requests
write command (note that _holding_register_configuration_index
is a variable):
requests.put('http://192.168.0.100/restapi/modbus/holding_registers/'+str(_holding_register_configuration_index)+'/name/',auth=auth,headers=headers,json='vrs6')
number | modbus/holding_registers/N/index/ |
Zero-based index of holding register (without 40...01 added) |
The value is subject to the following constraints: all of the following is true:
Retrieving the value is denied if not administrative user
Changing the value is denied if any of the following is true:
This number represents a value in persistent storage.
Sample requests
write command (note that _holding_register_configuration_index
is a variable):
requests.put('http://192.168.0.100/restapi/modbus/holding_registers/'+str(_holding_register_configuration_index)+'/index/',auth=auth,headers=headers,json=64822)
Sample curl
write command (note that :holding_register_configuration_index
is a URL template argument):
curl --digest -u admin:1234 -H "X-CSRF: x" -X PUT -H "Content-type: application/json" -H "Accept: application/json" --data-binary "57475" "http://192.168.0.100/restapi/modbus/holding_registers/:holding_register_configuration_index/index/"
sum (boolean) | modbus/holding_registers/N/allow_read/ |
Holding register is readable via Modbus/TCP |
Retrieving the value is denied if not administrative user
Changing the value is denied if any of the following is true:
This sum represents a value in persistent storage.
This sum can assume the following values:
constant true | Enabled | The feature is enabled | |
constant false | Disabled | The feature is disabled |
Sample uom
library read command (note that _holding_register_configuration_index
is a variable):
print(uom.dump(uom.modbus.holding_registers[_holding_register_configuration_index].allow_read))
⇒
false
Sample requests
read command (note that _holding_register_configuration_index
is a variable):
print(requests.get('http://192.168.0.100/restapi/modbus/holding_registers/'+str(_holding_register_configuration_index)+'/allow_read/',auth=auth,headers=headers).json())
⇒
False
sum (boolean) | modbus/holding_registers/N/allow_write/ |
Holding register is writable via Modbus/TCP |
Retrieving the value is denied if not administrative user
Changing the value is denied if any of the following is true:
This sum represents a value in persistent storage.
This sum can assume the following values:
constant true | Enabled | The feature is enabled | |
constant false | Disabled | The feature is disabled |
Sample JS request
read command (note that _holding_register_configuration_index
is a variable):
request.get({url:"modbus/holding_registers/"+_holding_register_configuration_index.toString()+"/allow_write/"},function(error,response,body) {console.log(body)});
⇒
true
Sample CLI read command (note that holding_register_configuration_index
is a variable):
uom get "modbus/holding_registers/${holding_register_configuration_index}/allow_write"
⇒
true
number | modbus/holding_registers/N/value/ |
State of holding register |
The value is subject to the following constraints: all of the following is true:
Retrieving the value is denied if not administrative user
Changing the value is denied if not administrative user
This number represents a value in persistent storage.
Sample CLI read command (note that holding_register_configuration_index
is a variable):
uom get "modbus/holding_registers/${holding_register_configuration_index}/value"
⇒
32248
Sample curl
write command (note that :holding_register_configuration_index
is a URL template argument):
curl --digest -u admin:1234 -H "X-CSRF: x" -X PUT -H "Content-type: application/json" -H "Accept: application/json" --data-binary "47851" "http://192.168.0.100/restapi/modbus/holding_registers/:holding_register_configuration_index/value/"
sum (optional number) | modbus/port/ |
TCP port to listen on, if any |
Retrieving the value is denied if not administrative user
Changing the value is denied if any of the following is true:
This sum represents a value in persistent storage.
This sum can assume the following values:
constant null | Use default port | Listen on TCP port 502 | |
number | Modbus broker port | TCP port to listen on | all of the following is true: |
Sample uom
library write command:
uom.modbus.port=null
Sample requests
read command:
print(requests.get('http://192.168.0.100/restapi/modbus/port/',auth=auth,headers=headers).json())
⇒
None
object | modbus/notifications/ |
Modbus-related notifications |
Retrieving the value is denied if not administrative user
This object does not support direct modification.
This object contains the following items:
parameter_kinds | Parameter kinds |
events | Events |
Sample requests
read command:
print(requests.get('http://192.168.0.100/restapi/modbus/notifications/',auth=auth,headers=headers).json())
⇒
{'events': {'dli.modbus.sample_event': {'parameters': [{'id': 'sample_parameter', 'has_fixed_value': False, 'fixed_value': None}], 'message_template': ['sample event']}}, 'parameter_kinds': {}}
Sample CLI read command:
uom get "modbus/notifications"
⇒
{"events":{"dli.modbus.sample_event":{"parameters":[{"id":"sample_parameter","has_fixed_value":false,"fixed_value":null}],"message_template":["sample event"]}},"parameter_kinds":[]}
object | modbus/notifications/parameter_kinds/ |
Kinds of event parameters |
This object does not correspond to an actual resource.
This object is empty.
map | modbus/notifications/events/ |
Event templates |
Retrieving the value is denied if not administrative user
This map is composite, i.e. is modified as a whole.
This map does not support direct modification.
This map contains Event elements.
Creating elements in this collection is not supported.
Sample CLI read command:
uom get "modbus/notifications/events"
⇒
{"dli.modbus.sample_event":{"parameters":[{"id":"sample_parameter","has_fixed_value":false,"fixed_value":null}],"message_template":["sample event"]}}
Sample JS request
read command:
request.get({url:"modbus/notifications/events/"},function(error,response,body) {console.log(body)});
⇒
{"dli.modbus.sample_event":{"parameters":[{"id":"sample_parameter","has_fixed_value":false,"fixed_value":null}],"message_template":["sample event"]}}
See also Events: Event
object | modbus/notifications/events/S/parameters/N/ |
Properties of a parameter associated with the event |
This object is a part of a composite value which is modified as a whole.
This object contains the following items:
id | Identifier |
has_fixed_value | Fixed value flag |
fixed_value | Fixed value |
Sample uom
library write command (note that _event
and _event_parameter_index
are variables):
uom.modbus.notifications.events[_event].parameters[_event_parameter_index]={fixed_value=null,has_fixed_value=false,id="sample_parameter"}
Sample JS request
read command (note that _event
and _event_parameter_index
are variables):
request.get({url:"modbus/notifications/events/"+_event+"/parameters/"+_event_parameter_index.toString()+"/"},function(error,response,body) {console.log(body)});
⇒
{"id":"sample_parameter","has_fixed_value":false,"fixed_value":null}
string | modbus/notifications/events/S/parameters/N/id/ |
Parameter identifier |
The value is subject to the following constraints: parameter kinds[the value]
Retrieving the value is denied if not administrative user
This string is a part of a composite value which is modified as a whole.
This string does not support direct modification.
Sample requests
read command (note that _event
and _event_parameter_index
are variables):
print(requests.get('http://192.168.0.100/restapi/modbus/notifications/events/'+_event+'/parameters/'+str(_event_parameter_index)+'/id/',auth=auth,headers=headers).json())
⇒
'sample_parameter'
Sample CLI read command (note that event
and event_parameter_index
are variables):
uom get "modbus/notifications/events/${event}/parameters/${event_parameter_index}/id"
⇒
"sample_parameter"
sum (boolean) | modbus/notifications/events/S/parameters/N/has_fixed_value/ |
Flag indicating that the parameter's value for this event is fixed |
Retrieving the value is denied if not administrative user
This sum is a part of a composite value which is modified as a whole.
This sum does not support direct modification.
This sum can assume the following values:
constant true | Fixed | The value is fixed | |
constant false | Variable | The value is variable |
Sample uom
library read command (note that _event
and _event_parameter_index
are variables):
print(uom.dump(uom.modbus.notifications.events[_event].parameters[_event_parameter_index].has_fixed_value))
⇒
false
Sample curl
read command (note that :event
and :event_parameter_index
are URL template arguments):
curl --digest -u admin:1234 -H "Accept: application/json" "http://192.168.0.100/restapi/modbus/notifications/events/:event/parameters/:event_parameter_index/has_fixed_value/"
⇒
false
sum (variant) | modbus/notifications/events/S/parameters/N/fixed_value/ |
Fixed parameter value for this particular event |
Retrieving the value is denied if not administrative user
This sum is a part of a composite value which is modified as a whole.
This sum does not support direct modification.
This sum can assume the following values:
constant null | Null | Null | |
constant true | True | True | |
constant false | False | False | |
string | String | This string | |
number | Number | This number |
Sample uom
library read command (note that _event
and _event_parameter_index
are variables):
print(uom.dump(uom.modbus.notifications.events[_event].parameters[_event_parameter_index].fixed_value))
⇒
null
Sample CLI read command (note that event
and event_parameter_index
are variables):
uom get "modbus/notifications/events/${event}/parameters/${event_parameter_index}/fixed_value"
⇒
null
object | modbus/notifications/events/S/ |
Event template |
This object is a part of a composite value which is modified as a whole.
This object contains the following items:
message_template | Message template |
severity | Severity |
parameters | Event parameters |
Sample uom
library read command (note that _event
is a variable):
print(uom.dump(uom.modbus.notifications.events[_event]))
⇒
{message_template={"sample event"},parameters={{fixed_value=null,has_fixed_value=false,id="sample_parameter"}}}
Sample CLI write command (note that event
is a variable):
uom set "modbus/notifications/events/${event}" "{\"parameters\":[{\"id\":\"sample_parameter\",\"has_fixed_value\":false,\"fixed_value\":null}],\"message_template\":[\"sample event\"]}"
array | modbus/notifications/events/S/message_template/ |
Template for human-readable message generation |
Retrieving the value is denied if not administrative user
This array is a part of a composite value which is modified as a whole.
This array does not support direct modification.
This array contains Message template element elements.
Creating elements in this collection is not supported.
Sample CLI read command (note that event
is a variable):
uom get "modbus/notifications/events/${event}/message_template"
⇒
["sample event"]
Sample JS request
read command (note that _event
is a variable):
request.get({url:"modbus/notifications/events/"+_event+"/message_template/"},function(error,response,body) {console.log(body)});
⇒
["sample event"]
sum (variant) | modbus/notifications/events/S/message_template/N/ |
Element of human-readable message template |
Retrieving the value is denied if not administrative user
This sum is a part of a composite value which is modified as a whole.
This sum does not support direct modification.
This sum can assume the following values:
string | String | Fixed string | |
number | Parameter | Index of message parameter to insert | event parameters[the value] |
Sample requests
read command (note that _event
and _message_template_element_index
are variables):
print(requests.get('http://192.168.0.100/restapi/modbus/notifications/events/'+_event+'/message_template/'+str(_message_template_element_index)+'/',auth=auth,headers=headers).json())
⇒
'sample event'
Sample JS request
read command (note that _event
and _message_template_element_index
are variables):
request.get({url:"modbus/notifications/events/"+_event+"/message_template/"+_message_template_element_index.toString()+"/"},function(error,response,body) {console.log(body)});
⇒
"sample event"
sum (enumerated number) | modbus/notifications/events/S/severity/ |
Severity rating assigned to the event |
Retrieving the value is denied if not administrative user
This sum is a part of a composite value which is modified as a whole.
This sum does not support direct modification.
This sum can assume the following values:
constant 1 | Emergency | Treat the event as an emergency | |
constant 2 | Alert | Treat the event as an alert | |
constant 3 | Critical | Treat the event as critical | |
constant 4 | Error | Treat the event as an error | |
constant 5 | Warning | Treat the event as a warning | |
constant 6 | Notice | Treat the event as a notice | |
constant 7 | Informational | Treat the event as informational | |
constant 8 | Debug | Treat the event as debugging-related |
Sample uom
library read command (note that _event
is a variable):
print(uom.dump(uom.modbus.notifications.events[_event].severity))
⇒
{}
Sample CLI read command (note that event
is a variable):
uom get "modbus/notifications/events/${event}/severity"
⇒
[]
array | modbus/notifications/events/S/parameters/ |
Additional data associated with the event |
Retrieving the value is denied if not administrative user
This array is a part of a composite value which is modified as a whole.
This array does not support direct modification.
This array contains Event parameter elements.
Creating elements in this collection is not supported.
Sample curl
read command (note that :event
is a URL template argument):
curl --digest -u admin:1234 -H "Accept: application/json" "http://192.168.0.100/restapi/modbus/notifications/events/:event/parameters/"
⇒
[{"id":"sample_parameter","has_fixed_value":false,"fixed_value":null}]
Sample requests
read command (note that _event
is a variable):
print(requests.get('http://192.168.0.100/restapi/modbus/notifications/events/'+_event+'/parameters/',auth=auth,headers=headers).json())
⇒
[{'id': 'sample_parameter', 'has_fixed_value': False, 'fixed_value': None}]
See also Event parameters: Event parameter